SPECIFICATION FOR UNIT CONTROL PANEL / SYSTEMS (UCP)

 装置控制面板/系统(UCP)规范



1. General Requirement

1、一般要求

Where defined in Control Schematic and I&C philosophy /design basis, packaged unit control shall be incorporated in a PLC based unit control panel (UCP). Otherwise, packaged equipment’s control shall be configured on BPCS and safety shall be implemented in ESD system.

在控制原理图和I&C理念/设计基础中定义的情况下,封装装置控制应并入基于PLC的装置控制面板(UCP)中。否则,包装设备的控制应在BOCS上进行配置,并在ESD系统中应用安全装置。

This section defines the basic outlines/specification for the Unit Control Panel. Supplier shall use this section as a reference and shall remain responsible for furnishing a comprehensive and functional system including all hardware / software components necessary to achieve the same, whether or not such requirements are explicitly mentioned in this document.

本章节定义了装置控制面板的基本要点/规范。供应商应使用本章节作为参考,并应继续负责提供一个全面的功能系统,包括所需的所有硬件/软件组件,无论此类要求是否在本文件中明确提及。

Control System as described in this Specification shall be provided by the Supplier for package skid. The UCP shall be mounted on packaged skid The system shall be a PLC based process control (Allen Bradley’s Control Logix) that includes a comprehensive set of proven algorithms and functional module auxiliaries to provide full control and monitoring and safety capabilities.

本规范中描述的控制系统应由供应商提供,用于包装滑轨。UCP应安装在包装滑轨上。控制系统应是基于PLC的过程控制(Allen Bradley控制逻辑),包括一套全面的经过验证的算法和功能模块辅助设备,以提供全面的控制和监控以及安全功能。

The PLC based control system shall have the capabilities for entire control & monitoring and safety needs of Packaged Unit. This include but not limited to monitoring of all field transmitters, operation/control of pumps, Motor's, control valves and related PID with feedback control, various Interlocks/Permissive that have to be implemented.

基于PLC的控制系统应具有封装装置所需的全部控制和监控以及安全能力。这包括但不限于所有现场变送器的监控,泵、电机、控制阀和具有反馈控制的相关PID的操作/控制,以及必须实现的各种联锁/许可。

The PLC control system shall have the capability to monitor, control, display, alarm and record all assigned plant inputs and outputs. The PLC system shall also be configured to handle all shutdown requirements of skid package by interfacing with the BPCS and ESD system.

PLC控制系统应具有监控、控制、显示、报警和记录所有指定设备输入和输出的能力。PLC系统该应配置为能够通过与BPCS和ESD系统的连接来处理滑轨包装的所有关闭要求。

The Supplier shall provide complete assembled system / marshalling cabinets, loaded with all necessary software (installed and configured) including all programming and calibration, as required.

供应商应按照需求提供完整的装配系统/编组柜,装载所有必要的软件(安装和配置),包括所有编程和校准。

For smaller packages, especially where field mounted local UCP is required, separate marshalling cabinet may not be required. In such cases, Package Supplier may provide marshalling terminals/relays within the system cabinet.

对于较小的包装,特别是在需要现场安装本地UCP的情况下,可能不需要单独的编组柜。在这种情况下,包装供应商可以在系统机柜中提供编组端子/继电器。

All instruments on the packaged equipment shall be wired up/connected to the UCP including packaged associated F&G detectors, shutdown valves and blowdown valves. UCP shall be interfaced with the main BPCS through serial communication protocol in combination with FO cable link where distance limitation does not allow for serial communication. BPCSHMI (by others) shall be used to display graphical screens / MIMIC of complete process within the package. In addition, a local HMI (Allen Bradley's Panel View),mounted on UCP's front, shall be provided in conjunction with required push buttons, lamps and selector switches.

包装设备上的所有仪器应接通电源到/连接到UCP,包括包装相关联的F&G检测器、关闭阀门和排污阀门。UCP应通过串行通信协议与主BPCS相连接,在距离限制不允许串行通信的情况下,与FO电缆链路相结合。BPCSHMI(由其他人)应用于在包装内显示完整过程的图形屏幕/ MIMIC。此外,安装在UCP前面的本地HMI(Allen Bradley面板视图)应与所需的按钮、灯具和选择器开关一起提供。

The UCP shall have the capability to transfer data for every IO to the BPCS to achieve the desired interface.

UCP应具有将每个IO数据传输到BPCS以实现所需接口的能力。

Although the UCP will remain responsible for complete control of the packaged process, supervisory controls may be afforded to BPCS, which may be exercised by the BPCS operator through its HMI. Supplier on final P&ID shall show any such requirements. Conversely, if such is a Contractor requirement, it will be shown on package specifications or reference P&IDs included in the Requisition Package.

虽然UCP将继续负责包装过程的全部控制,但是可以向BPCS提供监督控制,这可以由BPCS操作员通过HMI来执行。最终P&ID的供应商应显示任何此类要求。相反,如果这是对承包商的要求,则将显示在包装规范或包装要求中所含的P&ID参考中。

Where explicitly specified in main package specification/scope of work, UCP shall include a panel mounted local HMI / VDU (in addition to BPCS HMI) showing process MIMIC, IO status, diagnostics and alarms.

在主包装规范/工作范围明确规定的情况下,UCP应包括面板安装的本地HMI/VDU(除了BPCS HMI),显示过程MIMIC、IO状态、诊断和报警。

It shall be noted that PC-based engineering and operator workstations / consoles for Unit Controls are generally not required, unless stated otherwise in Package specifications/scope of work document. Such cases may arise, due to a large-scale package that may not be handled suitably on a door mounted HMI and annunciation panel. UCP shall also be responsible to achieve partial or complete shutdown (depending on ESD level) within Supplier's supplied package. The unit shutdown logic shall be designed, programmed and implemented within the UCP as elaborated in section 4.1.3 of this document.

应注意,除非在包装规范/工作范围文件中另有说明,一般不需要装置控制的基于PC的工程和操作员工作站/控制台。由于大型包装可能不能在安装HMI和通告面板的门上被适当地处理,因此可能出现这种情况。UCP还应负责在供应商提供的包装内实现部分或全部关闭(取决于ESD等级)。装置关闭逻辑应在UCP中进行设计、编程和实现,如本文第4.1.3节所述。

All signals related to USD/ESD communication between UCP and main ESD shall be hard-wired.

与UCP和主ESD之间的USD/ESD通信相关的所有信号应为硬连线。

To achieve automatic motor on-off, UCP shall provide digital output up to designated interposing relays/terminals of marshalling panel, where the motor control cable will be terminated according to motor control schematic.

为了实现自动电动机开关,UCP应提供数字输出到指定的插入式继电器/编组面板的端子,其中电动机控制电缆将根据电动机控制原理图终止。

However, the motor control schematic shall be furnished by this Supplier.

但是,电动机控制原理图应由本供应商提供。

Similarly, UCP panel shall also house designated marshalling terminals / IOs to receive motor status signals (on-off-trip) from MCC.

同样地,UCP面板还应该容纳指定的编组终端/IO,以从MCC接收电动机状态信号(开-关-跳闸)。

All interposing relays for the above mentioned bi-directional hard-wired links shall be provided within the UCP marshalling cabinet.

上述双向硬连线链路的所有插入继电器应在UCP编组柜内提供。

The supplier shall ensure the enclosure of UCP shall comply temperature requirement (122T). The ControlLogix, controller, module, HMI and all component shall comply.

供应商应确保UCP的外壳符合温度要求(122T)。ControlLogix、控制器、模块、HMI和所有组件均应符合。

No component shall be installed on sidewall of UCP. All components should be on front side.

UCP的侧壁上不得安装任何组件。所有组件应在前侧。

2. Technical Requirements

2、技术要求

The system shall generally comprise of standalone cabinets including:

系统通常包括独立的机柜,包括:

a) PLC Controller

a)PLC控制器。

b) PLC Analog, digital, thermocouple and pulse type input/output modules.

b)PLC模拟、数字、热电偶和脉冲型输入/输出模块。

c) Redundant Communication Equipments and cables.

c)冗余通信设备和电缆。

d) Redundant Power Supply Units.

d)冗余电源部件。

e) Panel mounted HMI panel.

e)安装HMI面板的面板。

f) Laptop for configuration of PLC / HMI pre installed with required softwares.

f)预装有所需软件的PLC/HMI配置的笔记本电脑。

g) Licensed Configuration / Application Software for whole system.

g)用于整个系统的许可配置/应用软件。

h) Input / Output Marshalling etc.

h)输入/输出编组等。

i) System Cabinet(s).

i)系统机柜。

j) OPC license for interfacing with Plant BPCS, where required.

j)在需要时与设备BPCS连接的OPC许可证。

k) Panel mounted VDU / HMI screen.

k)安装VDU/HMI屏幕的面板。

The System shall employ redundancy for all critical system modules including:

系统应为所有关键系统模块使用冗余,包括:

a) Redundant communication buses between controller and I/O modules.

a)控制器和I/O模块之间的冗余通信总线。

b) Dual redundant power supplies, operating on load sharing basis.

b)在负载共享基础上工作的双冗余电源。

c) Redundant communication equipment and control network.

c)冗余通信设备和控制网络。

Supplier shall supply all interconnecting cables, with plug-in connections at each end, required between the Control system equipment and auxiliary equipment including input/output Marshalling Cabinets.

供应商应为控制系统设备和辅助设备(包括输入/输出编组柜)之间需要插入式连接提供所有互连电缆。

All Supplier supplied equipment shall have EMI/RFI suppression and shall comply with industry regulation on RFI suppression.

所有供应商提供的设备应具有EMI/RFI抑制,并应符合RFI抑制的行业法规。

Supplier shall supply all special tools, any hardware or software and test equipment required for installation and startup.

供应商应提供安装和启动所需的所有特殊工具、任何硬件或软件和测试设备。

The system shall be prewired and ready for field termination. The system shall be supplied for the following requirements as a minimum.

系统应预先布线并准备好现场端子。系统应至少具备以下要求。

3. System Hardware Requirements

3、系统硬件要求

The system shall be designed in a modular scheme. Supplier shall ensure that it shall be possible to isolate and remove any faulty or malfunctioning module without interrupting proper function of the control system.

系统应以模块化方案进行设计。供应商应确保可以隔离和移除任何缺陷或故障模块,而不会中断控制系统的正常功能。

The system shall be based on PLC controllers and certified for IEC 61131 (all parts). The system shall employ redundant data bus for communication between controllers and I/O modules.

系统应基于PLC控制器,并经IEC 61131(所有零件)认证。 系统应采用冗余数据总线用于控制器和I/O模块之间的通信。

Replacement and installation of controller shall be possible without shutting down of the control system.

控制器的更换和安装应能在不关闭控制系统的情况下进行。

The controllers shall be selected such that processor loading does not exceed 60% when all control / monitoring loops and external interfaces are active.

应选择控制器,使得当所有控制/监视回路和外部接口有效时,处理器负载不超过60%。

The controllers and I/O modules shall have LED indications for running, fault, etc for ease of maintenance.

控制器和I/O模块应具有运行、故障等LED指示灯,以便于维护。

All modules shall have plastic non-static casing for mechanical protection during storage, installation or removal.

所有模块应具有塑料非静态外壳,以便在存储、安装或拆卸期间进行机械保护。

All controller modules shall have their own independent power supply, battery-backed RAM and watchdog timer for maximum system availability.

所有控制器模块都应有自己独立的电源、带电池的RAM和看门狗定时器,以最大限度地提高系统可用性。

Analog module cards shall not have more than eight channels per module. Digital module cards shall not have more than sixteen channels per module.

模拟模块卡中的每个模块不得超过8个通道。 数字模块卡中的每个模块不得超过16个通道。

The analog I/O modules shall be selected for 24V DC 4-20mA signal loop powered instruments.

模拟I/O模块应选择24V DC 4-20mA信号回路供电仪器。

The digital modules shall be selected for 24V DC input / output dry contacts. However, isolation relays shall be provided between digital I/O modules and end devices.

应选择数字模块用于24V直流输入/输出干触点。但是,应在数字I/O模块和终端设备之间提供隔离继电器。

I/O modules quantity shall have 15% additional spare capacity after complete utilization for future expansion.

I/O模块数量在完全利用后将有15%的额外备用容量用于将来扩展。

Redundant communication equipment shall be provided for interfacing between controller, engineering / operator workstation and existing control system. The system shall be capable of using open industry communication protocols (MODBUS, ProfiBus, TCP/IP etc).

应提供冗余通信设备,用于控制器、工程/操作员工作站和现有控制系统之间的接口连接。系统应能够使用开放工业通信协议(MODBUS,ProfiBus,TCP / IP等)。

There shall be at least two Fiber optic ports (TCP/IP protocol) available for Purchaser use. These ports do not include ports used by package Supplier for his use.

应至少有两个光纤端口(TCP/IP协议)供买方使用。这些端口不包括包装供应商自己使用的端口。

4. System Software Requirements

4、系统软件要求

Suppler shall provide software for complete monitoring and control of the package equipment.

供应商应提供软件,用于包装设备的完全监控和控制。

The monitoring software shall utilize different levels of access for process operators / supervisor, and configuration engineers. These levels of access shall be password protected.

监控软件应为过程操作员/监督员和配置工程师使用不同级别的访问。这些访问级别应受密码保护。

Operator access shall be for plant operator. This level of access shall allow the user to view the process parameters and instrument face plates. User shall also be allowed to modify process set points and control loop gains.

操作员访问应为设备操作员。这种访问级别应允许用户查看过程参数和仪器面板。用户还被允许修改过程设定点和控制回路增益。

Engineering mode shall allow the user to configure new loops or modify existing control strategies in the configuration software. Modification of control strategies and parameters shall be available online.

工程模式应允许用户在配置软件中配置新的回路或修改现有的控制策略。控制策略和参数的修改应在线提供。

The controller programming language shall utilize functional block diagrams as minimum. All programming languages shall be certified for IEC 61131-3.

控制器编程语言至少应使用功能框图。所有编程语言均应通过IEC 61131-3认证。

The software shall have complete diagnostic capabilities of the control system. It shall be possible to view the status of all installed hardware and I/O channels on main BPCS HMI (to which this UCP shall be interface), and isolate them if necessary from the engineering workstation of BPCS. CPU loading shall also be viewable on the engineering workstation of BPCS.

软件应具有控制系统的完整诊断能力。它应可以查看主BPCS HMI上的所有已安装硬件和I/O通道的状态(UCP必须与之相连),并在必要时将其与BPCS的工程工作站隔离。CPU负载也应在BPCS的工程工作站上查看。

The software shall have auto-tuning feature for adjustment of control loops.

软件应具有自动调节功能,用于控制回路的调节。

It shall be possible to change any loop from auto control to manual control (through BPCS HMI). Manual control feature shall allow the BPCS operator to force an output to the final control element.

它应可以将任何回路从自动控制更改到手动控制(通过BPCS HMI)。手动控制功能将允许BPCS操作员将输出强加到最终控制元件。

Supplier shall provide all required software with lifetime licenses in favor or the Contractor. Supplier shall keep soft copies of all project documentation (start-up manuals, termination drawings, loop drawings, technical manuals etc) on a separate drive on the engineering and operator workstation for easy access.

供应商应为所有需要的软件提供有效的终身许可证或将其提供给承包商。供应商应在工程和操作员工作站的单独驱动器上保存所有项目文件的软拷贝(启动手册,终端图,回路图,技术手册等),以便于访问。

5. Power Requirements

5、电源要求

Supplier shall provide dual redundant power supplies working on load sharing basis. The power supplies shall be provided with reverse protection diodes for isolation of failed power supply.

供应商应提供负载共享基础上的双冗余电源。电源应装备反向保护二极管,用于隔离故障电源。

The power supplies should be selected such that one power supply can cater for the power requirement of the complete system and field instrumentation. Each power supply shall be sized to 30% above the maximum power requirement of control system and field instrumentation.

应选择电源,使一个电源可满足整个系统和现场仪表的电源要求。每个电源的尺寸应大于控制系统和现场仪表的最大功率要求的30%。

Purchaser will provide 120VAC, 60Hz power inputs from plant UPS. Supplier is responsible for conversion from 120VAC to the required voltage levels.

买方将提供来源于设备UPS的120VAC,60Hz电源输入。供应商负责将120VAC转换为所需的电压水平。

Power supply running and fault indications shall be interfaced with the PLC controller for viewing on HMI.

电源运行和故障指示应与PLC控制器连接,以便在HMI上查看。

Power wiring shall be such that it shall be possible to isolate any independent module for troubleshooting and diagnostic.

电源接线应能够隔离任何独立的模块以进行故障排除和诊断。

6. Cabinet Requirements

6、机柜要求

Supplier shall provide cabinets for system components and marshalling / termination equipment. The cabinet shall be of Rittal make. For indoor mounting, the cabinet shall be rated for IP42 as a minimum. For outdoor mounting, panel shall be IP65 and suitable for applicable hazardous area classification. The IP rating shall be applicable after installation of panel mounted switches, ventilation fans and filters, or any other equipment which is required to be installed on cabinet front, side or back panels.

供应商应为系统组件和编组/终端设备提供机柜。机柜应为Rittal 制造。对于室内安装,机柜应至少达到IP42等级。对于室外安装,面板应为IP65,并适用于适用的危险区域分类。在安装开关面板、通风风扇和过滤器或任何其他需要安装在机柜前面、侧面或后面板上的设备之后,IP等级应适用。

Cabinet doors shall be latched type with tamperproof lock.

柜门应为带防盗锁的锁定型。

Cabinets shall be provided with bottom cable entries.

机柜应装备底部电缆入口。

Cabinet tag shall be clearly stamped on traffolyte plate and fixed on panel front.

机柜标签应清晰地印在traffolyte板上并固定在面板前部。

All switches for manual process over-ride shall be fitted to panel front door. Override switches shall be key-operated type.

用于手动过程的所有开关应安装在面板前门上。超控开关应为钥匙操作型。

System modules, surge protector and terminal shall be installed on DIN rails inside the panel, installed on side plate are not permitted. Adequate space shall be available inside the cabinet for easy maintenance.

系统模块、浪涌保护器和端子应安装在面板内的DIN导轨上,不允许安装在侧板上。机柜内应有足够的空间,便于维护。

System modules shall be installed in groups for clear identification. All equipment shall be clearly tagged.

系统模块应分组安装以便清楚识别。所有设备应清晰标记。

All terminal rows shall be clearly tagged and labeled. Terminal rows and wire ducting shall be segregated for analog signals, digital signals, and power cables.

所有端子排应清楚地标记并贴上标签。端子排和电线管道应按模拟信号、数字信号和电源电缆进行隔离。

Ensure there space between terminal block and cable duct must have space for control cable tag (such as TT-110101A), space of handling wires.

确保接线端子和电缆槽之间必须有控制电缆标签(如TT-110101A)的空间和处理电线的空间。

Terminals used in the marshalling cabinet shall be Weidmuller or equivalent suitable for up to 2.5sqmm cable. All analog terminals shall be knife-out type, whereas digital signal and power terminals shall be fused with appropriately rated fuse.

编组柜中使用的端子应为Weidmuller或适用于高达2.5平方毫米电缆的等价物。 所有模拟端子应为刀型,而数字信号和电源端子应与适当额定值的保险丝熔接。

Internal wiring shall be color coded for signal identification. Each termination shall have ferrule or sleeve marked with the relevant tag. All wire tags, terminal numbers and module tags shall match the loop wiring drawings submitted by Supplier.

内部接线应进行颜色编码,用于信号识别。每个端子应有标有相关标签的套圈或套筒。所有电线标签、端子号和模块标签应与供应商提交的回路接线图相匹配。

Spare I/O cards shall also be pre-wired up to the marshalling terminal strips and clearly marked on the loop drawings.

备用I/O卡也应预先连接到编组端子排,并在回路图纸上清楚标记。

Wire ducting shall have 40% spare capacity for ease of maintenance and future use. Separate earth copper bars shall be provided on the cabinet bottom for signal ground and cabinet body earth.

电线管道应具有40%的备用容量,便于维护和将来使用。机柜底部应有独立的接地铜条,用于信号地线和机柜地线。

Metal pocket shall be available inside the cabinet door for A3 sized documents.

对于A3尺寸的文件,柜门内应有金属袋。

7. Panel Mounted HMI

7、安装HMI的面板

HMI display (Allen Bradley’s PanelView) shall be colored screen and touch type having communication ports for Ethernet and modbus, USB ports, etc. The PC shall be pre¬loaded with all requisite licensed HMI and application software.

HMI显示(Allen Bradley的面板视图)应为彩色屏幕和触摸式类型,具有用于以太网和modbus、USB端口等的通信端口。PC应预先加载所有必需的授权HMI和应用软件。

The PC/HMI shall also have the provision to optionally connect external Keyboard and mouse.

PC/HMI还应准备可选择地连接外部键盘和鼠标。

A window shield should be covered to avoid sunlight impact.

窗户罩应予以遮盖,以避免阳光影响。

This UCP mounted HMI shall generally be able to display complete process MIMIC including but not limited to:

安装在UCP上的HMI通常应能够显示完整过程MIMIC,包括但不限于:

Display of all transmitter indications.

显示所有变送器指示。

All Process and safety alarms.

所有过程和安全警报。

Valve Status.

阀门状态。

Motor Status, including duty / standby status.

电机状态,包括工作/待机状态。

IO status and Diagnostics.

IO状态和诊断。

Shutdown status.

关闭状态。

Any active system over-rides.

任何有源系统超控。

It should also be possible from this HMI to re-configure (as a minimum):

它也可以从该HMI进行重新配置(至少):

All PID control loops.

所有PID控制回路。

All transmitter set points.

所有变送器设定点。

Duty / Standby selection of pumps / motors.

泵/电机的工作/待机选择。

• All other standard functions required by the operator for necessary operation, depending on type of packaged equipment.

•操作员根据包装设备的类型进行必要操作所需的所有其他标准功能。

HMI shall also include, for each motor, following controls:

HMI还应包括每个电机的以下控制:

Soft switches for motor's manual start - stop from control room.

软开关,用于电机在控制室的手动启动-停止。

Duty / Standby Selection Soft Switch.

•  工作/待机选择软开关。

8. Annunciator System

8、信号器系统

When an annunciator is provided on UCP or Local Panel, the following shall apply:

当在UCP或本地面板上提供信号器时,应适用以下条件:

1) Alarm annunciator sequence shall be designed in accordance with ANSI/ISA 18.1 M, (alarm only lock-in facilities), and F, (first failure or first-up alarm groups). For alarm acknowledge, first-up reset and lamp-test shall be hardwired via potential free contact inputs from the local control panels.

1)报警信号器序列应根据ANSI / ISA 18.1 M(仅报警锁定设施)和F(首次故障或初次报警组)进行设计。对于报警确认,首次复位和灯具测试应通过本地控制面板的无源触点输入进行硬连线。

2) Pushbuttons for "Acknowledge", "First-out Alarm Reset', and "Lamp Test" shall be provided (3) The annunciator system shall provide an output so that a common group alarm or common group trip alarm for indication in the control room.

2)“确认”、“首次报警复位”和“灯具测试”的按钮应予以提供。(3)信号器系统应提供一个输出,以便在控制室中显示一个公共组报警或公共组跳闸报警。

3) Regular alarms and shutdown alarm on annunciators shall be separated.

3)信号器上的常规报警和停机报警应予以分开。

4) Each annunciator shall be supplied with a relay to actuate audible device, here specified in the relevant requisition. The audible device shall be a suitable sound level for outdoor use in a refinery, i.e. more than 110 dBA.

4)每个信号器应配备继电器以驱动声音设备,特此在相关要求中指定。声音设备应具有在户外炼油厂使用的合适声级,即大于110dBA。